With the meter set on 2K and one lead connected to any end of the widing and the other to a given earth point as depicted in diagram below
The reading must read infinity this means that there is no circuit between the winding and ground ( earth)
Any other reading means that the winding has shorted to earth.
If it has shorted to earth the winding either needs to be replaced or rewound.
————————————————————————————————————————
Connections & result of internal circuit resistance testing windings:
With the meter set on 200Ω connect the 2 probes together and get the internal resistance of the meter and leads for example 0.2Ω. This reading will need to be taken away from the actual reading to give you the true resistance value of the winding.
Connect on probe to one end of the winding and the other to the other end as depicted in the diagram below.
The reading in the diagram above is 3.8Ω but it isn't the true resistance. The internal resistance for example of 0.2Ω must be taken away giving a result of 3.6Ω. This is the true resistance and must be within the manufacturer specification.
There are four possible result that you can get when doing an internal winding resistance test, they are:
Within specification
Open circuit
Lower resistance than Spec
Higher resistance than Spec
Within specification means that the winding has past this test and can be used again.
An open circuit result means there is break in the winding. This requires that the winding is either replaced or rewound; breaks in winding are very rarely repaired. Refer to the diagram below.
Lowe than specified resistance indicates an internal short result. This means that there is break in the insulation of the winding, it hasn't shorted to ground but has shorted to another part of the winding as illustrated in the diagram below.This allows the current to take a shorter path through the winding effectively lowering the resistance below Manufacturers specifications
This requires that the winding is either replaced or rewound.
Higher than specified resistance can indicate poor winding connection. This could mean there is dirt or corrosion where the winding ends are connected, thus causes a higher than normal resistance.
Poor connections at the ends of the winding may be able to be repaired by removing them and cleaning up the connection points and re-soldering as necessaryWill be given another starter motor and it should also be tested before dismantling.
————————————————————————————————————————
No Load Test:
Mount the starter in a test bench, carry out no load test then enter your meter readings in the chart below.
NO LOAD TEST MANUFACTURERS SPECIFICATIONS NO LOAD TEST RESULT
Voltage No less than 11volts 11.70V
Current 30 to 50 Amps 37.6A
Label the components:
A. Commutator
B. Roller-type/ overruning clutch
C. Brush spring/ Carbon brush.
————————————————————————————————————————
Disassembly:
Disassemble the starter in the correct sequence as demonstrated by your lecturer. Failure to follow the correct sequence and procedures may result in damage to the starter motor.
Sequence:
1. Scribe alignment marks along the two end housings and field housing (main body) of the starter motor, this will help to align the major compinents.
2. Remove M terminal wire from the solenoid ( this wire connects the output from the solenoid to the starter motor)
3. Scribe alignment marks on the solenoid body and mounting then remove solenoid
4. Remove any screws in the commutator end housing ( failure to do this can result in major damage to the brushes or field windings).
5. Remove commutator end housing
6. Remove brushes as necessary to remove brush plate assembly
7. Remove field coil housing ( main body of the starter motor)
8. Remove shift fork from drive end housing ( it is important that you mark the position of the shift fork)
9. Remove the armature assembly
10. Remove the overruning clutch from the shaft ( clean any burrs with emery paper for easy removal of the clutch)
————————————————————————————————————————
Testing Armature
Visual Inspection:
Visual Inspection- Check for signs of:
Overheating
Burning
Physical damage of insulation and coil windings
Poling
COMPONENT TEST REPORT
ARMATURE MANUFACTURER'S SPECIFICATIONS TEST RESULTS SERVICEABLE
Overheating Visual Inspection No signs of overheating No
Burning Visual Inspection No signs of burning No
Physical damage Visual Inspection The insulation was
damaged onto the poling Yes
Poling Visual Inspection The poling has been
damaged by the insulation Yes
————————————————————————————————————————
Ground Circuit Tests:
Use a multi-meter in the ohms range and check for:
Ground Short circuit between each of the commutator segments and the amature core or shaft
ARMATURE GROUND TEST
MANUFACTURER'S SPECIFICATIONS TEST RESULTS SERVICEABLE
Infinity infinity Yes
————————————————————————————————————————
Continuity Circuit Test
With the ohmmeter in the same range check continuity between one of the commutator segments while moving the second probe around on each of the other commutator segments.
ARMATURE CONTINUITY TEST
MANUFACTURER'S SPECIFICATIONS TEST RESULTS SERVICEABLE
0-1Ω 0Ω Yes
————————————————————————————————————————
Testing Commutator:
Measure the Commutator diameter and check the mica undercut depth as necessary.
COMMUTATOR TEST
MANUFACTURER'S SPECIFICATIONS TEST RESULTS SERVICEABLE
Minimum diameter 28.8~31mm 31.5mm Yes
Mica Undercut 0.7~1.0mm 0.7mm Yes
————————————————————————————————————————
Check Armature Shaft for run out:
To check for run-out, place the armature between the "v" blocks.
Turn the armature 360° while reading the dial test indicator set up on the armature core as indicated by the arrow
ARMATURE RUNOUT TEST
MANUFACTURER'S SPECIFICATIONS TEST RESULT SERVICEABLE
0~0.2mm 0.05mm Yes
————————————————————————————————————————
Alternative Method of Testing Armature
Using 48 volt test Light
Continuity test keep one of the probes on one segment and move the other probe around each of the other segments. ( This test applies greater pressure to the windings and should be used where available) The test light should glow.
Ground test place one probe on any commutator segment and the other on either the armature core or shaft. The test light should not glow.
ARMATURE CONTINUITY AND GROUND TEST
MANUFACTURER'S SPECIFICATIONS TEST RESULT SERVICEABLE
Continuity Test Light on over each segment Yes,The light on. YES
The commutater
segment are connected
Ground Test Light Off Yes,The light off YES
The commutater
segment aren't
connceted the armature
cove
————————————————————————————————————————
Testing for internal short circuit using growler:
1. Place the armature on the "V" of the growler.
2. Turn the switch on to Growler position.
3. Hold a hacksaw blade or metal strip along the armature and rotate the armature.
ARMATURE INTERNAL SHORT TEST
MANUFACTURER'S SPECIFICATIONS TEST RESULTS SERVICEABLE
Hacksaw blade will vibrate when placed over Hacksaw which means YES
shorted winding indicating a shorted armature shorted winding indicating
a shorted armature
————————————————————————————————————————
Field Coil and Pole Shoes
Visual Inspection- Check for signs of:
Overheating
Burning
Physical damage of insulation and coil windings
Poling
COMPONENT TEST REPORT
FIELD COILS AND MANUFACTURER'S TEST RESULTS SERVICEABLE
POLE SHOES SPECIFICATIONS
Overheating Visual Inspection No signs YES
Burning Visual Inspection No signs YES
Physical damage Visual Inspection There was a damage No
for the field coil
Poling Visual Inspection The field coil has some YES,can be fixed
damage
————————————————————————————————————————
Test the Field coils for Continuity:
Checking for continuity in the field winding place the probes on each end of the field winding
Depending on the design of starter motor circuit, field winding maybe ground or insulated from the field housing.
COMPONENT TEST REPORT
FIELD COILS MANUFACTURER'S TEST RESULTS SERVICEABLE
CONTINUITY SPECIFICATIONS
If Grounded TEST N/A N/A N/A
Not Grounded 0~0.02Ω 0Ω YES
————————————————————————————————————————
Test the Field coils for grounding:
Ifthe field winding to ground test can be preformed ( the field winding is not attached to the body of the starter motor). Place the positive probe on the field wire or brush, then the common probe on the body of the starter. The meter should read Infinity.
COMPONENT TEST REPORT
FIELD COILS MANUFACTURER'S TEST RESULTS SERVICEABLE
GROUNDING SPECIFICATIONS
If Grounded 0~0.02Ω N/A N/A
Not Grounded Infinity Infinity YES
————————————————————————————————————————
Brushes:
Measure the length of the brushes and inspect for cracks and other damage.
Brushes sometimes have a scribed line on one face or refer to specification sheet for allowable length.
Note: When considering the brushes for replacement, remember that the starter may not be removed from a vechicle for over 100,000Km's. If the brushes are close to the minimum you should replace. New brushes are about 14mm long.
COMPONENT TEST REPORT
BRUSHES MANUFACTURER'S TEST RESULTS SERVICEABLE
SPECIFICATIONS
MINIMUM 5mm 15.9/15.9/15.9/- YES
LENGTH
————————————————————————————————————————
Brush Holder Assembly
To check for short circuit between insulated brushes and holder set the Ohms meter on the lowest resistance. Place one of the probes on the brush and the other on the metal retaining plate.
COMPONENT TEST REPORT
BRUSH HOLDER MANUFACTURER'S TEST RESULTS SERVICEABLE
ASSEMBLY SPECIFICATIONS
Grounded Holder 0~0.02Ω 0.1Ω No
Insulated Holder Infinity Infinity YES
————————————————————————————————————————
Solenoid Magnetic Switch:
Identify terminals: "B" Battery Supply, "S" ignition/ starter switch supply and "M" starter motor supply.
Note: M terminal will have a wire going into the solenoid switch Pull in winding Test:
connect 9V power supply between S and M terminals
Note this test is done with reduced voltage and for a maximum of 5 seconds to prevent heat damage to the winding
COMPONENT TEST REPORT
PULL IN WINDING MANUFACTURER'S TEST RESULTS SERVICEABLE
SPECIFICATIONS
Current Draw 8~12Amps 9.1A YES
Physical Action The Plunger should pull in The plunger pull in YES
————————————————————————————————————————
Hold in Test
Connect 9V power supply between S and solenoid body
Note this test is done with reduced voltage and a maximum of 5 seconds to prevent heat damage to the winding
Push the plunger in by hand and then release it.
COMPONENT TEST REPORT
HOLD IN WINDING MANUFACTURER'S TEST RESULTS SERVICEABLE
SPECIFICATIONS
Current Draw 5~8Amps 10.9A No
Physical Action The Plunger should The plunger was YES
remain in. still inside
When the power is When the power is
disconnected the plunger disconnected the
should release. plunger shoot out
————————————————————————————————————————
Pinion gear and Overruning or one way clutch:
Check pinion for gear damage and smooth movement along the armature shaft.
Turn the pinion gear in the direction of motor rotation, the clutch should free wheel and against direct of rotation it should lock.
Brushes:
To check bushes for wear, insert the end of the armature shaft into the appropriate end housing bush to and assess the shaft to bush clearance.
COMPONENT TEST REPORT
DRIVE MANUFACTURER'S TEST RESULTS SERVICEABLE
SPECIFICATIONS
Pinion Gear Visual Inspection The pinion gear is good YES
Bushes Visual Inspection Bushes was damaged NO
Clutch Visual Inspection Clytch was good YES
————————————————————————————————————————
Assembly:
Re-assemble the Starter Motor:
1. Lubricate the bushes.
2. Assembly in the reverse order of dismantling.
3. Note: Align marks when assembling the shift fork and the two end housings to the field body
4. Hold the brush springs back with a steel wire in the form of book. This will enable brush to be slid on the commutator
5. Do not over tighten any through bolts and screws.
Armature Thrust Clearance:
Check Armature Thrust Clearance. Check the Clearance with seal, spring and lock plate in place.
Pinion to Collar Clearance:
Mount the starter on the testing machine. Connect power only to S terminal. This will move the pinion out towards the collar without armature turning.
————————————————————————————————————————
Final no load test:
Mount the starter in a test bench, carry out no load test then enter your meter readings in the chart below.
NO LOAD TEST MANUFACTURER'S NO LOAD TEST RESULTS
SPECIFICATIONS
Voltage No less than 11 volts 11.47V
Current 30~50Amps 46.7A
Dose the starter motor run within manufacturers specifications YES
————————————————————————————————————————
The no load test is good, no any problems. In testing armature, we had some physical problems with the insulation, that was damaged onto the field coil cover. In the ground circuit test, it was gread, no problems and no damages. The alternative method of testing armature also looks good, field coil and pole shoes testing we have same problem as the testing armature, it's about the field coil cover. We broken the brushes when we was doing the brushes test, but we fixed that finaly.
Rajamane Industries Pvt Ltd is a leading manufacturer of Oil skimmer, coolant pump in India. Company has grown in the past decade with its various diversifications in the field of auto-electricals, Oil skimmer, BLDC Motor, Motor rewinding manufacturers and Special electrical mortars
回复删除Motor rewinding manufacturers
Coolant pump manufacturers
Rajamane
Bldc Motor manufacturers
Oil skimmer manufactures
Alternator Repair Services
For more details visit :-
www.rajamane.co/hegde
This blog is very good because good information on all described products. We have similar product that you can visit us
回复删除Motor rewinding manufacturers
This blog is very good because good information on all described products. We have similar product that you can visit us
回复删除Motor rewinding manufacturers
This blog is very good because good information Oil skimmer manufactures.We have similar product that you can visit usMotor Rewinding Repair Services,Alternator Repair Services
回复删除thanx, For your post it is very information waiting for your nest post
回复删除PHYSICS ELECTRICITY
There are many frameworks to write tests in, and continuous integration software will run tests automatically every time code is checked into a version control system. martindale abrasion tester
回复删除